Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM03027
Parcel: 13329001A

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T07CM03027
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2007 TERRY STEVENS ZONING REVIEW Passed
07/17/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
07/17/2007 THAUSER1 FIRE REVIEW Needs Review
07/17/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/17/2007 THAUSER1 OUT TO CUSTOMER Completed