Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03023
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 07/18/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide additional information regarding the process occurring in the hood (e.g. spraying) and MSDS information for the materials being used. 2. Show the location of the hood within the building and the distances from the exhaust fan to property lines and building openings. 3. Provide the fan/hood calculations. |
| 07/18/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T07CM03023 7/18/07 1. Provide MSDS Sheets. 2. Plans Examiner will check about the propriety of Fire Marshall involvement. |
| 07/18/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/18/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1) Please provide the denoted MSDS sheet for the Class II combustible liquid per section 106.1.1 of the 2006 IBC. 2) Please revise the code references to the currently adopted codes for the City of Tucson per section 106.1.1 of the 2006 IBC (i.e. 2006 IBC, IFC, IMC, IECC, UPC and 2005 NEC). 3) Please provide an overall floor plan that shows where this work is occuring per section 106.1.1 of the 2006 IBC. 4) Please revise the ramp referenced in detail 2/A1.1 to provide the required clear floor space for the pull side of the new double doors per section 404.2.3 of ANSI 117.1-2003. 5) Please provide additional information regarding the sign shop walls and opening protection per section 106.1.1 of the 2006 IBC. The current submittal indicates fire dampers for the ducts entering/exiting this space, but no information was provided indicating that the wall infill had to be a rated assembly. |
| 07/18/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
| 07/18/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/18/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 08/29/2007 | GBONILL1 | FIRE | REVIEW | Needs Review | |
| 08/29/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |