Permit Number: T07CM03023
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03023
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2007 HEATHER THRALL ZONING REVIEW Approved
07/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide additional information regarding the process occurring in the hood (e.g. spraying) and MSDS information for the materials being used.
2. Show the location of the hood within the building and the distances from the exhaust fan to property lines and building openings.
3. Provide the fan/hood calculations.
07/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review T07CM03023 7/18/07

1. Provide MSDS Sheets.
2. Plans Examiner will check about the propriety of Fire Marshall involvement.
07/18/2007 ROBERT SHERRY WATER REVIEW Approved
07/18/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Needs Review 1) Please provide the denoted MSDS sheet for the Class II combustible liquid per section 106.1.1 of the 2006 IBC.

2) Please revise the code references to the currently adopted codes for the City of Tucson per section 106.1.1 of the 2006 IBC (i.e. 2006 IBC, IFC, IMC, IECC, UPC and 2005 NEC).

3) Please provide an overall floor plan that shows where this work is occuring per section 106.1.1 of the 2006 IBC.

4) Please revise the ramp referenced in detail 2/A1.1 to provide the required clear floor space for the pull side of the new double doors per section 404.2.3 of ANSI 117.1-2003.

5) Please provide additional information regarding the sign shop walls and opening protection per section 106.1.1 of the 2006 IBC. The current submittal indicates fire dampers for the ducts entering/exiting this space, but no information was provided indicating that the wall infill had to be a rated assembly.
07/18/2007 RSHERRY1 WWM REVIEW Passed
07/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/18/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/29/2007 GBONILL1 FIRE REVIEW Needs Review
08/29/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review