Permit Number: T07CM03018
Parcel: 12809005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03018
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
07/17/2007 LOREN MAKUS ENGINEERING REVIEW Approved
07/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03018 7/24/07

1. Reproduce with architectural backgrounds.
2. Provide panel and circuit number for all circuits on Lighting plan.
3. Add Fixture E to Lighting Fioxture Schedule.
4. Provide power requirements for ceiling fans.
5. Fill in load information on panel schedule for A-1.
6. Panel A does not show on the electrical plans.
07/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/24/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the text size on all plan sheets to a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson.

2) Please provide safety glazing for the interior windows adjacent to doors 102A and 103A per section 2406.3 of the 2006 IBC.

3) Please provide additional information regarding the restroom accessibility to ensure complete accessibility or indicate on the cover sheet compliance with section 3409.6 regarding spending 20% upgrading accessibility.

4) Please coordinate the keynotes on sheet A1.0 per section 106.1.1 of the 2006 IBC.

5) Please revise all of the code references to cite the 2006 I-codes.
07/24/2007 ROBERT SHERRY WATER REVIEW Approved
07/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/24/2007 RSHERRY1 WWM REVIEW Passed
07/24/2007 DAVE MANN FIRE REVIEW Approved
07/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2007 GERARDO BONILLA OUT TO CUSTOMER Completed