Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03018
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/17/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03018 7/24/07 1. Reproduce with architectural backgrounds. 2. Provide panel and circuit number for all circuits on Lighting plan. 3. Add Fixture E to Lighting Fioxture Schedule. 4. Provide power requirements for ceiling fans. 5. Fill in load information on panel schedule for A-1. 6. Panel A does not show on the electrical plans. |
| 07/24/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/24/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please revise the text size on all plan sheets to a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson. 2) Please provide safety glazing for the interior windows adjacent to doors 102A and 103A per section 2406.3 of the 2006 IBC. 3) Please provide additional information regarding the restroom accessibility to ensure complete accessibility or indicate on the cover sheet compliance with section 3409.6 regarding spending 20% upgrading accessibility. 4) Please coordinate the keynotes on sheet A1.0 per section 106.1.1 of the 2006 IBC. 5) Please revise all of the code references to cite the 2006 I-codes. |
| 07/24/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/24/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/24/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
| 07/24/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/26/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |