Permit Number: T07CM03013
Parcel: 13337017F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM03013 8/8/07

1. Indicate the date of Revision 2 on the plans. Reference R4 30-304 Arizona State Board of Technical Registration.
2. Provide location of electrical service and TEP transformer on scaled plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2007 DELMA ROBEY APPROVAL SHELF Completed
09/06/2007 DELMA ROBEY OUT TO CUSTOMER Completed