Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM03013
Parcel: 13337017F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03013 8/1/07

1. Available faulrt current for a 208V 1000A TEP pad-mounted electrical service is 55,600A, not 42,000.
2. Provide location of electrical service entrance section and TEP transformer on scaled drawings.
08/01/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/01/2007 DAVE MANN FIRE REVIEW Approved
08/01/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/08/2007 GERRY KOZIOL WWM REVIEW Approved