Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03013
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03013 8/1/07 1. Available faulrt current for a 208V 1000A TEP pad-mounted electrical service is 55,600A, not 42,000. 2. Provide location of electrical service entrance section and TEP transformer on scaled drawings. |
| 08/01/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/01/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/01/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/08/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |