Permit Number: T07CM03012
Parcel: 13014446A

Address:
3910 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03012
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
07/31/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/31/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
08/01/2007 DROBEY1 WWM REVIEW Needs Review
08/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03012 8/1/07

1. Fault calculations result 76934AIC at new panel. This can not be correct. Also please note that "c" value corresponds to a non-metallic conduit for the service entrance conductors. Please re-evaluate.
2. Provide location of electrical service entrance section and TEP transformer on scaled drawings.
08/01/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/01/2007 DROBEY1 FIRE REVIEW Needs Review