Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03012
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/17/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Coordinate the duct insulation requirements shown on sheet M2.1 with the Specifications shown on sheet M3.2. The minimum duct insulation shall conform to the requirements of Section 503.2.7, IECC 2006. 3. Coordinate the balancing requirements shown on sheet M2.1 with the specifications on sheet M3.3. The final balance shall ensure that adequate ventilation is provided to the project areas. 4. Clarify the note regarding the electric wall heaters noted on sheet M2.1 but not shown on either the mechanical or electrical designs. |
| 07/17/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Complete the water calculations shown on sheet P2.1. 3. Clarify the arrangement for the exam room sinks - tempered water (TMV-1) or instantaneous water heater (detail 3/P2.1)? There is no electrical service for any water heaters. 4. Provide specifications for the exam room sinks. The specifications for water closets for use in Puerto Rico are not required. |
| 07/17/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/17/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please revise the text within the plans to be a minimum of 1/8" in height and all capital letters in accordance with the submittal requirements for the City of Tucson. 2) Please provide the required clear floor space on the pull side of the door for room #2 in accordance with section 4040.2.3 of ANSI 117.1-2003. |
| 07/17/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/31/2007 | VFLORES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/31/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 07/31/2007 | VFLORES1 | FIRE | REVIEW | Needs Review | |
| 07/31/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |