Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02966
Parcel: 13101002H

Address:
5000 E 29TH ST

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T07CM02966
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2007 MARTIN BROWN FIRE REVIEW Approved
07/20/2007 RAY MAJUTA BUILDING-COMMERCIAL REVIEW Denied 1) Please seal each sheet of the plans in accordance with section 106.1.1 of the 2003 IBC and the Arizona State Board of Technicial Registration.

2) Please coordinate the information between the plans and calculations per section 106.1.1 of the 2003 IBC as the current submittal indicates that the tower is located in Maracopa County.

3) Please provide connection information for the new antenna per section 106.1.1 of the 2003 IBC.
07/23/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/25/2007 Michael Wyneken PLANNING-CITY HALL REVIEW Denied 1. Submit fully dimensioned drawings per condition b. of the Decision Letter dated June 27, 2007. The note states the standoff is 18", however, the drawing appears to show it as greater.

2. Clarify that cables will run through the interior of the pole as required in condition c. It appears the cables come out of the top of the pole and extend downward, on the exterior to the antennae.

3. Add note stating the pole-mounted equipment will be painted to match the existing pole.

4. Why does the engineering review statethe tower is located in Maricopa County, AZ?
07/26/2007 JAY HOGAN COMMUNICATIONS REVIEW Approved
08/06/2007 TERRY STEVENS ZONING REVIEW Denied 08/13/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The Cell Tower site plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Special Exception section and Structural section of DSD.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
09/21/2007 GERARDO BONILLA REJECT SHELF Completed