Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM02964
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/05/2008 | DAVE MANN | FIRE | REVIEW | Denied | Some portions of the building are greater than 300 feet hose lay from the new hydrant. This is more than allowed for an unsprinklered building. Show other hydrants or provide sprinklers. |
| 05/07/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/09/2008 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 05/09/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/09/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 05/09/2008 | SHANAE POWELL | REJECT SHELF | Completed |