Permit Number: T07CM02952
Parcel: 108214280

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02952
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2007 STEVE SHIELDS ZONING REVIEW Approved
07/13/2007 LOREN MAKUS ENGINEERING REVIEW Approved
07/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02952 7/18/07

1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. Lettering is barely legible.
2. Fill in load on panel schedule for receptacle on Ckt 16.
3. Fill in load on panel schedule for Fc-1, on Ckt 17.
4. Electrical load on Ckt 1 appears to be 900, not 720 VA.
07/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/18/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the font size to a minimum of 1/8" in height per section 106.1.1 of the 2006 IBC.

2) Please indicate if the facility is completely accessible or provide information on how 20% will be spent upgrading the accessibility in accordance with section 3409.7 of the 2006 IBC.
07/18/2007 ROBERT SHERRY WATER REVIEW Approved
07/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/18/2007 RSHERRY1 WWM REVIEW Passed
07/20/2007 DAVE MANN FIRE REVIEW Approved
07/23/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review