Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2007 GERRY KOZIOL WWM REVIEW Approved
08/08/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM02947

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

Construction drawing guidelines are available from the residential desk of the Development Services Division.

As of 6/12/2007 the City of Tucson has adopted the 2006 IRC with the exception of the plumbing portion which has been replaced with the 2006 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

· This permit requires the installation of smoke alarms if not existing, R313.2.1.

SITE PLAN:

1. Show the water pipe size from the meter to the building. Show the point of connection for the proposed hot and cold branches. The pipe must be sized for the calculated load, 2006 UPC 610.1.

STRUCTURAL PLANS:

1. Completely detail all connections (R301.1) to the foundation and roof framing.
2. Show masonry wall horizontal lateral support R606.9.1.
3. Show masonry wall vertical lateral support R606.9.2.
4. Provide existing rafter sizes in compliance with Table R802.5.1 for applying a ceiling.
5. Show existing rafter size and spacing or any added support for the attic mounted equipment, R801.2.

ELEVATIONS:

1. Show the location of roof/ceiling insulation. Provide an attic space calculation and specify size and location of all vents needed to comply (if vented attic), R806.2.
2. Specify type of gable-end vents and apply appropriate net opening reductions (free area shall be considered 75% of the gross area for metal louvers and 25% for wood louvers), M1701.5.

SECTIONS - DETAILS:

1. Note or detail interior wall and ceiling covering (½" GWB), R702.3.
2. Provide fiber-cement board rather than moisture resistant (green) gypsum board in tub and shower areas, R702.4.2.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2006 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code.
2. Provide water pressure range and diameter of water line from the meter, UPC 610.8, Table 6-6.
3. Provide the new water line diameter and point of connection per UPC 610.8.

MECHANICAL PLANS:

1. Show supply and return ducts with minimum R-8 insulation, R1103.2.1.
2. Show provisions for and route secondary condensate drain, M1305.1.3 & M1411.3.1.

ELECTRICAL PLANS:

1. Show the location of the sub-panel on the plan, E3501.6.2.
2. Note that only approved outlet boxes may be used for ceiling fans, E4001.6.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show the "R" values of insulation, as well as the "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC, N1101.2.
2. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.75, ceiling R=30 and walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior. Show these values and the solar heat gain coefficient SHGC minimum value of 0.40, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
08/13/2007 GERARDO BONILLA REJECT SHELF Completed