Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02917
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/06/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | 1) Please provide additional information for emergency power for egress illumination in accordance with section 1006.3 of the 2006 IBC for the entire tenant space. Please be sure to provide the emergency power for the lights on the exit discharge side of the required exits. |
| 08/06/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Correct drafting errors for the duct design to show intent. Reference Section 106.3.1, IMC 2003. 2. Provide a certified balance report for the mehanical system. Reference Section 403.3.4, IMC 2003. 3. Revise the ventilation calculations; the music practice rooms are not dresing rooms. Reference Section 403.3, IMC 2003. |