Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02917
Parcel: 13314236C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02917
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2007 HEATHER THRALL ZONING REVIEW Approved
07/23/2007 RSHERRY1 WWM REVIEW Passed
07/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/23/2007 ANY ENGINEERING REVIEW Approved
07/23/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please indicate on the plans the total costs associated for this project ans show that either 20% of the cost has been spent increasing accessibility or that the facility is fully accessible per section 3409.7 of the 2006 IBC.COMMENT REMAINS: Please provide verification that the installation of the grab bars and toilet paper and paper towel dispensers will cost the denoted $3,600 in order to verify compliance with section 3409.7 (i.e. construction estimates, etc.).

2) Please provide additional information regarding the location of exit signage and emergency power for egress illumination in accordance with sections 1011 and 1006.3 of the 2006 IBC for the entire tenant space. Please be sure to provide the emergency power for the lights on the exit discharge side of the required exits. COMMENT REMAINS: The current submittal still doesn't provide any information regarding the emergnecy power for the egress illumination, both on the interior and exterior side of the new tenant space. Please revise in accordance with section 1006.3 of the 2006 IBC.
07/23/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not adequately addressed. Provide calculations to show that the revised ductwork will distribute the specified air flow quantities within the capabilities of the existing air conditioner. Reference Section 603.2, IMC 2003.
2. Clarify the airflow quantities for the existing diffusers.
3. Revise the ventilation calculations per Sections 403.3 and 403.3.2, IMC 2003, using the appropriate occupancies (e.g. retail sales, basement and street).
4. Revise the font size to a minimum of 1/8", all uppercase.
07/24/2007 DAVE MANN FIRE REVIEW Approved
08/03/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2007 DELMA ROBEY OUT TO CUSTOMER Completed