Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02910
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/11/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the restroom has adequate ventilation per Section 403.3, IMC 2003. |
| 07/11/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the size, route, and termination point of the T&P relief for the existing water heater. 2. Specify the mixing valve to be used for the lavatory, show how it is to be installed, and specify the temperature setpoint. 3. Revise the minimum font size to 1/8" (all uppercase). |
| 07/11/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/11/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/11/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 07/12/2007 | VFLORES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/12/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 07/12/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |