Permit Number: T07CM02910
Parcel: 11305069A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02910
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2007 TERRY STEVENS ZONING REVIEW Approved
07/11/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the restroom has adequate ventilation per Section 403.3, IMC 2003.
07/11/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the size, route, and termination point of the T&P relief for the existing water heater.
2. Specify the mixing valve to be used for the lavatory, show how it is to be installed, and specify the temperature setpoint.
3. Revise the minimum font size to 1/8" (all uppercase).
07/11/2007 ROBERT SHERRY WATER REVIEW Approved
07/11/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
07/11/2007 ANY ENGINEERING REVIEW Approved
07/12/2007 VFLORES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/12/2007 VFLORES1 WWM REVIEW Needs Review
07/12/2007 DAVE MANN FIRE REVIEW Approved
07/12/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review