Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM02875
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/09/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please revise the denoted use from A-3 to A-2 per section 303 of the 2003 IBC. 2) Please coordinate the structural callout on the north end between the structural plan and the associated details per section 106.1.1 of the 2003 IBC. |
07/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
07/09/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
07/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information regarding the continuation of the existing gas line located below the new patio roof. Reference Section 103.2.3, UPC 2003. |
07/09/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
07/09/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
07/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/12/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |