Permit Number: T07CM02865
Parcel: 11103018B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02865
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2007 HEATHER THRALL ZONING REVIEW Approved
07/06/2007 ANY ENGINEERING REVIEW Approved
07/09/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please provide stair, guard and handrail information in order to verify compliance with sections 1009, 1012 & 1013 of the 2006 IBC.

2) Please coordinate the building area, occupant load and construction type throughout the plans in accordance with section 106.1.1 of the 2006 IBC. The current submittal has different area sizes and a conflict with the construction type (IIIB vs. VB).

3) Please provide a wall section per section 106.1.1 of the 2006 IBC.

4) Please provide accessible egress from the shop area per chapter 10 of the 2006 IBC.

5) Please provide the mechanical installation in accordance with section 106.1.1 of the 2006 IBC.

6) Please indicate that the means of egress to the public way is accessible or specify on the plans how the 20% will be spent increasing accessibility in accordance with section 3409.7 of the 2006 IBC.

7) Please provide a COMcheck for the builing envelope for the addition in order to verify compliance with the 2006 IECC.

8) Please provide information regarding the exit signage and egress illumination with emergency power in order to verify compliance with sections 1011 and 1006 of the 2006 IBC.

9) Please provide calculations for the dock area retaining wall and show how the new sections connect to the existing per section 106.1.1 of the 2006 IBC.
07/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/30/2007 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/30/2007 ROBERT SHERRY WATER REVIEW Approved
07/30/2007 DROBEY1 FIRE REVIEW Denied
07/30/2007 RSHERRY1 WWM REVIEW Passed
07/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/30/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed