Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02843
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/09/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/11/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. The Panel L2 feeder originates at Panel MDP according to the Panel MDP schedule, the One Line Diagram, and the Electrical Load Summary. However, this Panel is on the Panel L1 schedule. Please clarify. 2. Please revisit the 0.1 KVA load requirements for the Printer, Ckt L1-9. 3. It does not appear that there is a Maintenance receptacle for Ac-1 or EC-1. 4. The disconnect for the Ice Machine is shown as a receptacle on the Power Plan, but is called for as a NEMA 1 on the Electrical Feeder Schedule. Please clarify. |
07/30/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Dimension setbacks from building to property lines. 2. Justify exterior wall construction per tables 602 and 704.8 of the 2003 IBC. 3. Show accessible route to public way and from any accessible parking spaces into the building per 2003 IBC section 1104.1 4. Indicate in keynote 6 detail 17/A6.1 that existing roof framing should be 16" TJI 210 @ 16" o.c. 5. Change room finish schedule and room finish legend pp A8.2 to meet 2003 IBC section 1210.1 and 1210.2. Epoxy painted gypsum is not considered a hard non-absorbent surface. 6. Section 1210.5 of the 2003 IBC does not allow toilet rooms to open directly into a food preperation area. |
08/06/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/06/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide material standards for all plumbing fixtures (and kitchen equipment connected to the plumbing system) being provided by others. Reference Section 401.1, UPC 2003. 2. Coordinate the water fixture units used for the water calculations and the plumbing fixture schedule. Reference Section 103.3.2, UPC 2003. 3. Clarify the plumbing connection requirements for K-5 and K-6. Reference Section 103.3.2, UPC 2003. 4. Revise the waste connection of K-1 to connect downstream of the trap arm of the floor sink. Reference Section 311.4, UPC 2003. 5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer and ice maker). Reference Section 609.10, UPC 2003. 6. Specify the slope of the horizontal rainwater pipes. Reference Section 103.2.3, UPC 2003. 7. Revise the termination of the primary rainwater leader so that it doesn't cross over the sidewalk. Reference Section 4.4 F, City of Tucson Development Standard No. 3-01.0. 8. Show that the inlet level of the secondary (overflow) drain complies with Section 1101.11.2.3, UPC 2003. |
08/06/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide specifications for the Type I hood. Reference Section 106.3.1, IMC 2003. 2. Provide the installed weight of the two supply air plenums for the exhaust hood. Reference Section 106.3.1, IMC 2003. 3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units (AC-1 and EC-1). Address the issue of the apparent overlap of the support area for the exhaust hood, the two supply air plenums for the hood, and AC-1. Reference Section 302.1, IMC 2003. 4. Recirculation of ventilation air from toilet rooms is prohibited. Reference Section 403.2.1 (3), IMC 2003. 5. Revise detail 1/A1.1 to show stainless steel panels extending 18" beyond the exhaust hood in all directions. Reference Section 507.9, IMC 2003. Note for future submittals: ventilation calculations using ASHRAE 62.1-2004 require the use of the default population values and combined outdoor rate values from Table 6-1. Reference Section 403.3, IMC 2003, as amended by the City of Tucson. |
08/07/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | NEEDS 8TH FLOOR CREDIT EVALUATION |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/10/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |