Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02835
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/12/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. RESUBMITTALS MUST INCLUDE ORIGINALLY SUBMITTED PLANS. 2. PREVIOUS COMMENTS CONCERNING CONFUSION WITH ACCESSIBILITY STILL APPLY. PLEASE CLARIFY COMPLIANCE WITH 2003 ANSI 117.1: A) MUST FILE AN APPEAL TO PROIDE BOTTLED WATER IN LIEU OF DUAL LEVEL ACCESSIBLE DRINKING FOUNTAIN. B) JUSTIFY ON PLAN THAT COMMON AND PRIVATE RESTROOMS HAVE CORRECT TURN AROUND CLEARANCES. YOU MAY NOT HAVE RADIUS GO OVER A TOILET AND MAY ONLY ENCROACH UNDER A LAVATORY 8". C) SINK IN LOUNGE 106 MUST BE ACCESSIBLE. D) PLEASE INDICATE ACCESSIBLE ROUTES FROM PUBLIC WAY PER 2006 IBC SECTION 1104.1. CLARIFY DETECTABLE WARNINGS AND PROPER CURB RAMPS. WALKWAY SLOPE PERCENTAGES WOULD BE NICE. E) CLARIFY THAT ALL PUBLIC ENTRANCES ARE ACCESSIBLE PER SECTION 1105.1 OF THE IBC. 3. LETTERING ON SHEETS A-1 AND A-3 TOO SMALL, 1/8" FONT MINIMUM IS REQUIRED. 4. PROVIDE ALL BUILDING STATISTICS AS PER DSD REQUIREMENTS. 5. EXPLAIN SCOPE OF DEMOLITION WORK IN PLAN AND ELEVATION. 6. CLARIFY HOW SOUTH AND EAST EXTERIOR WALLS MEET REQUIREMENTS OF 2006 IBC, TABLE 602 INCLUDING SECTIONS 704.11 AND 705.6. 8. STRUCTURAL REVIEW A. ENTRY DETAIL A/3 AND NORTH ELEVATION ON SHEET A-3 SHOULD BE REVISED TO INCLUDE ALL INFOMATION INDICATED ON STRUCTURAL ENGINEER'S DETAILS ON SUBMITTED CALCULATIONS, PAGES 1, 3 AND 4. B. GENERAL NOTES ON SHEET A-3 SHOULD BE REVISED TO INCLUDE SPECIFICATIONS FOR WOOD. |
| 12/13/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Tucson Water records indicate that the meter serving this address is a 5/8" meter, not a ¾" meter. Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project (22.5 fixture units equates to a demand of 16 GPM). |
| 12/13/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Second request; no architectural details found in the drawing set. Coordinate with the Architect and show how the fan coils are being connected to the building structure. Provide calculations to show that the building structure is not being adversely affected. Reference Section 302.1, IMC 2006. 2. The guards shown on sheet A-3 do not meet the requirements of Section 304.10. Provide structural calculations and attachment details for the railing. 3. Comment not addressed. HP-1 and FC-1 do have independent outside air intakes but they supply ventilation to diverse occupancy types. Provide calculations to show that the common ventilation systems for HP-1 and FC-1 are sized in accordance with Section 403.3.2, IMC 2003. |
| 12/13/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. According to Tucson Water, the water pressure range for this address is 68 to 75 PSI, not 81 PSI. Water pipe sizing shall be based upon the minimum available pressure. Reference Section 610.7, UPC 2006. 2. Provide an approved appeal to the building official allowing the use of a bottled water dispenser and a single drinking fountain in lieu of a water cooler that complies with the requirements of Section 1109.5.1, IBC 2006. 3. Coordinate water closets shown in the plumbing plan, the water isometric, and the plumbing schedule with the waste and vent isometric. Reference Section 1109.2, IBC 2006. |
| 12/31/2007 | SREEVES1 | WWM | REVIEW | Needs Review | NEEDS 8TH FLOOR CREDIT EVALUATION |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/02/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 01/02/2008 | SHANAE POWELL | REJECT SHELF | Completed |