Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM02830
Parcel: 12418162D

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM02830
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02830 7/19/07

1. If panels are designated for future use, note as such on plans. Otherwise, show electrical loads with panel and circuit designations, and panel schedules.
2. Grounding Electrode Systems for new and existing services shall be bonded together.
3. It appears that the new and existing services are separated by a wall. Please specify the placards called for in NEC 230.2 (E). Provide the EXACT WORDING.
4. If the generator needs circuits for battery charging, starting, as such, please provide them on the plans.