| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02830 7/19/07 1. If panels are designated for future use, note as such on plans. Otherwise, show electrical loads with panel and circuit designations, and panel schedules. 2. Grounding Electrode Systems for new and existing services shall be bonded together. 3. It appears that the new and existing services are separated by a wall. Please specify the placards called for in NEC 230.2 (E). Provide the EXACT WORDING. 4. If the generator needs circuits for battery charging, starting, as such, please provide them on the plans. |