Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02816
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/10/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/18/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/25/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/25/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide the installed weight of the rooftop air conditioning units. Reference Section 106.3.1, IMC 2003. 3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the exhaust hood and exhaust fan EF-1. Reference Section 302.1, IMC 2003. 4. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. 5. Revise the ventilation calculations to take into account the different occupancy loads handled by Gas Pack #2 (Dining and Corridor). Reference Sections 403.3 and 403.3.2, IMC 2003. 6. Provide information from the manufacturer of the Gas Packs to show that units #1 and #2 are capable of operating with the scheduled flow rates for outside air. Reference Section 304.1, IMC 2003. 7. Provide specifications for Gas Pack #3. Reference Section 106.3.1, IMC 2003. 8. Show that the hood installation complies with Section 507.10, IMC 2003. 9. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2003. 10. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2003. 11. Provide information to show how the condensate drain system has been sized. Reference Section 307.2.2, IMC 2003, as amended by the City of Tucson. 12. Show how the gas vent for the water heater is to be terminated. Reference Section 510.6.2, UPC 2003. |
| 07/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide water supply isometrics. Reference Section 103.2.3, UPC 2003. 3. Install the flow control device for the hydromechanical grease interceptor per the manufacturer's instructions. Reference Section 301.1.1, UPC 2003. 4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003. 5. The submitted water pressure calculations are not supported by the water calculations for the shell plans and neither set of calculations supports the size of the water piping; revise the calculations and the pipe sizes as required. Reference Section 610.1, UPC 2003. 6. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (e.g. P4) and for changes in direction greater than 135 degrees (e.g. the hydromechanical grease interceptor). Reference Sections 707.4, 707.5, and 707.8, UPC 2003. 7. Specify the backflow protection for appliances connected to domestic water (e.g. Note 16, sheet P1, coffee brewer). Reference Section 103.2.3, UPC 2003. 8. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference Section 609.10, UPC 2003. |
| 07/31/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please indicate the number of tables and seats in the non-fixed seating area and revise the occupant load accordingly in accordance with section 1004 of the 2003 IBC. It appears that three tables would fit in this area and per section 1004.1.1 would need to be added to the occupant load accordingly. 2) Please provide verification that the rear exit is accessible in accordance with section 1007 of the 2003 IBC. The reference set of civil plans indicate a +4" elevation difference between the finish floor elevation and the grade immediately outside of the exits, but the reference set of architectural plans indicate no elevation difference. 3) Please provide verification that the egress illumination with emergency power has been provided at teh exit discharge side of the exits adjacent to the exits per section 1006.3 of the 2003 IBC. 4) Please provide structural verification that the existing structural system can support the new hood and associated exhaust fan in accordance with section 106.1.1 of the 2003 IBC. The shell building plans allow for mechanical units within a central band of the roof, with limitations, and this equipment is outside of that area. 5) Please provide verification that the new mechanical units within the specified band denoted on the shell building plans complies with the limitations of the shell structural plans per section 106.1.1 of the 2003 IBC. The shell plans limit the mechanical units to two 1500# units per beam and a number of the mechanical units do not specify their weight. |
| 08/01/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/06/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/06/2007 | DELMA ROBEY | REJECT SHELF | Completed |