Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02815
Parcel: 117144380

Address:
768 S MEYER AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING-WALKTHRU

Permit Number - T07CM02815
Review Name: RESIDENTIAL BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/11/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
07/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/23/2007 STEVE SHIELDS ZONING REVIEW Approved
07/23/2007 SSHIELD1 NPPO REVIEW Passed