Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM02814
Parcel: 11105245C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02814
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02815 7/3/07

1. Place panel calculations on the plans, minimum font size 1/8". Reference Section 302.3, Uniform Administrative Code, 1997.
2. If this were single phase, 120V to ground, line-to-line voltage would be 240V. for the Mechanical Unit a total of 5313 watts is not reasonable, because the unit would draw only 22.1A. Would not be on a 100A breaker. Reference NEC 430.52.
3. The 1800W Water Heater would draw 7.5A. Overcurrent protection undersized per NEC 422.11 (E).
4. See the attached for single phase 3-wire panel connections. Setup of load calculations does not demonstrate that no phase is overloaded.
5. Add 25% for continuous loads and for largest motor.
07/23/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/23/2007 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
07/23/2007 CAGUILA1 WWM REVIEW Needs Review