Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02814
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/03/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02815 7/3/07 1. Place panel calculations on the plans, minimum font size 1/8". Reference Section 302.3, Uniform Administrative Code, 1997. 2. If this were single phase, 120V to ground, line-to-line voltage would be 240V. for the Mechanical Unit a total of 5313 watts is not reasonable, because the unit would draw only 22.1A. Would not be on a 100A breaker. Reference NEC 430.52. 3. The 1800W Water Heater would draw 7.5A. Overcurrent protection undersized per NEC 422.11 (E). 4. See the attached for single phase 3-wire panel connections. Setup of load calculations does not demonstrate that no phase is overloaded. 5. Add 25% for continuous loads and for largest motor. |
07/23/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
07/23/2007 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
07/23/2007 | CAGUILA1 | WWM | REVIEW | Needs Review |