Permit Number: T07CM02814
Parcel: 11105245C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02814
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2007 HEATHER THRALL ZONING REVIEW Approved
07/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02814 7/2/07

1. Provide load calculations for the panel. Demonstrate that no phase is overloaded.
2. Provide voltage level for dishwasher and heater, and all other electrical requirements.
07/02/2007 ROBERT SHERRY WATER REVIEW Approved
07/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/02/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a floor drain in the scullery. Reference Sections 412.2.2 and 704.3, UPC 2003.
2. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference Sections 304.0 and 801.2, UPC 2003.
3. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference Section 707.4, UPC 2003.
4. Provide cleanouts sized per Section 707.11, UPC 2003.
07/02/2007 DAVE MANN FIRE REVIEW Approved
07/03/2007 DROBEY1 WWM REVIEW Needs Review
07/03/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/03/2007 DELMA ROBEY APPROVAL SHELF Completed
07/03/2007 DELMA ROBEY OUT TO CUSTOMER Completed
07/03/2007 DELMA ROBEY REJECT SHELF Completed