Permit Number: T07CM02804
Parcel: 11460041A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02804
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please provide sheet A2 as referenced throughout the plans per section 106.1.1 of the 2003 IBC in order to verify compliance with chapters 10, 11, and 12 of the 2003 IBC and ANSI 117.1-2003. COMMENT REMAINS: Please provide the dimensional placement for the rear and side wall grab bars in order to verify compliance with sections 604.5.1 and 604.5.2 of ANSI 117.1-2003. Please revise the height of the wet bar sink in accordance with section 1109.3 of the 2006 IBC and section 606.3 of ANSI 117.1-2003. Please revise the size of the font within the door and room finish schedules to be a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson. Please specify the size of the water closet grab bars in order to verify compliance with section 609 of ANSI 117.1-2003. Please coordinate the detail referenced within keynotes 10.11 and 10.12 as they reference the window schedule instead of the typical fixture heights.
07/12/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show that a separation of at least ten feet exists between air intake openings and
exhaust openings. Reference 401.5, IMC 2003.
2. Comment not addressed. Provide information on the sequence of operation for the restroom exhaust ("wall
switch time clock"?) to show that recirculation of the air from the restroom will
not occur. Reference Section 403.2.1, IMC 2003.
3. Comment not addressed. Show how adequate access is being provided for the equipment located on the roof
(the architectural drawings indicate the presence of a roof hatch but no ladder).
Reference Section 306.5, IMC 2003.
07/12/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/23/2007 DROBEY1 ENGINEERING REVIEW Needs Review
07/23/2007 DROBEY1 ZONING REVIEW Needs Review
07/23/2007 DROBEY1 WWM REVIEW Needs Review
07/23/2007 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/23/2007 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2007 DELMA ROBEY APPROVAL SHELF Completed
07/23/2007 DELMA ROBEY OUT TO CUSTOMER Completed
07/23/2007 DELMA ROBEY REJECT SHELF Completed