Permit Number: T07CM02804
Parcel: 11460041A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02804
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/03/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference 401.5, IMC 2003.
2. Provide information on the sequence of operation for the restroom exhaust ("wall switch time clock"?) to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
3. Show how adequate access is being provided for the equipment located on the roof (the architectural drawings indicate the presence of a roof hatch but no ladder). Reference Section 306.5, IMC 2003.
07/03/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the route and termination of the T&P relief pipe for the water heater.
2. Provide details of the water heater support (i.e. it is not shown on the architectural drawings).
3. Provide a drinking fountain.
07/03/2007 ROBERT SHERRY WATER REVIEW Approved
07/03/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please provide a drinking fountain in accordance with table 2902.1 of the 2003 IBC.

2) Please provide verification that the window adjacent to the conference room door complies with section 2406 of the 2003 IBC.

3) Please provide structural verification that the existing structural components can support the loads associated with the new mechanical units per section 106.1.1 of the 2003 IBC.

4) Please provide sheet A2 as referenced throughout the plans per section 106.1.1 of the 2003 IBC in order to verify compliance with chapters 10, 11, and 12 of the 2003 IBC and ANSI 117.1-2003.

5) Please provide details/sections for the support of the water heater over room 115 per section 106.1.1 of the 2003 IBC.

6) Please provide a COMcheck for the mechanical installations in order to verify compliance with the 2003 IECC. A free downloadable copy of COMcheck is available at www.energycodes.gov.
07/12/2007 DROBEY1 WWM REVIEW Needs Review
07/12/2007 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/12/2007 DROBEY1 ENGINEERING REVIEW Needs Review
07/12/2007 DROBEY1 ZONING REVIEW Needs Review
07/12/2007 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2007 DELMA ROBEY APPROVAL SHELF Completed
07/12/2007 DELMA ROBEY OUT TO CUSTOMER Completed
07/12/2007 DELMA ROBEY REJECT SHELF Completed