Permit Number: T07CM02786
Parcel: 116060960

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM02786
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Values filled in for Note 1 on Sheet 2 pertain to the Array Specifications. Should pertain to the System Specifications. Reference Sheet 3, and NEC 690.53.

2. Grounding Electrode Conductor shall be unspliced, not spliced as it appears across the TEP meter. Reference Sheet 2, NEC 690.47 (B), and NEC 250.166.

3. Plans indicate that the fused disconnect does not pertain to this project. See the note on the line diagram, and Note 8 on Sheet 2. If this is the case, it needs to be demonstrated that the Sunpower Inverter does not produce backfeed current. Please provide this documentation. Reference NEC 690.9 Exception (B).

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2007 DELMA ROBEY APPROVAL SHELF Completed
08/17/2007 DELMA ROBEY OUT TO CUSTOMER Completed
08/17/2007 GERARDO BONILLA REJECT SHELF Completed