Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM02786
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Values filled in for Note 1 on Sheet 2 pertain to the Array Specifications. Should pertain to the System Specifications. Reference Sheet 3, and NEC 690.53. 2. Grounding Electrode Conductor shall be unspliced, not spliced as it appears across the TEP meter. Reference Sheet 2, NEC 690.47 (B), and NEC 250.166. 3. Plans indicate that the fused disconnect does not pertain to this project. See the note on the line diagram, and Note 8 on Sheet 2. If this is the case, it needs to be demonstrated that the Sunpower Inverter does not produce backfeed current. Please provide this documentation. Reference NEC 690.9 Exception (B). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/17/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 08/17/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/17/2007 | GERARDO BONILLA | REJECT SHELF | Completed |