Permit Number: T07CM02781
Parcel: 10408078C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM02781
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm02781 9/26/07

1. Water Heater as annotated on Sheet MP.2 specifies 15.5A, for which overcurrent protection shall not exceed 25A. Electrical load information indicates a 26.9A WH, for which required overcurrent protection may not exceed 45A. Please clarify. Reference NEC 422.11 (E).