Review Details: REVISION - - 1ST
Permit Number - T07CM02781
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm02781 9/26/07 1. Water Heater as annotated on Sheet MP.2 specifies 15.5A, for which overcurrent protection shall not exceed 25A. Electrical load information indicates a 26.9A WH, for which required overcurrent protection may not exceed 45A. Please clarify. Reference NEC 422.11 (E). |
| 09/26/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |