Permit Number: T07CM02778
Parcel: 129122440

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM02778
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2007 BUREAU VERITAS 2ND PARTY REVIEW REVIEW Denied August 3, 2007 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T07CM02778
Bureau Veritas Job No. 01007-161001.067

Richard Noperi
3900 Deaver Rd.
Tucson, AZ 85735


Re: Plan Review: New Duplex
Address: 1138 32nd St.


Dear Sir:

Bureau Veritas North America has completed a Firstreview of the following documents on behalf of the City of Tucson:

Plans: One (1) set of building plans (10 sheets, 1 through 10) not sealed or dated.

Structural Calculations: None submitted with this review.

Truss Calculations: None submitted with this review


These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and Tucson amended 2006 IRC, 2006 IMC, 2005 NEC and 2006 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas North America



Shelley Knuffke
ICC Plans Examiner










SKK:sk
Re: Stories: One
Occupancy: R-3/VB
Building Area (sq. ft.): 2130 (livable)

2130 Total sq. ft.

A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2006 International Building Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

GENERAL REQUIREMENTS:

1. The City has adopted the 2006 codes. Plans must reflect the current code.

ELEVATIONS:

Provide height dimensions for roofline, headers, top plate and finished floor. IRC Section R106.

FOUNDATION PLAN COMMENTS:

Soils report is referred to on sheet 3 (foundation plan) but not included in submittal.

Detail one on page 5 is referenced on foundation sheet. Sheet 5 does not contain any details.

Foundation plates and sills shall be bolted to the foundation with minimum ½ inch bolts at 6 feet or less on center and embedded a minimum 7 inches into the foundation. IRC Section R403.1.6.

Show required holddowns, as specified on lateral design or as required for all alternate braced wall panels, on foundation plan. IRC Sections R106.1, R403.1.6 and 403.1.6.1.

PLUMBING COMMENTS:

1 .Note and specify that shower area walls shall be finished with a non-absorbent surface to a height of six feet above the floor. IRC R307.2.

Note and specify that all toilet, bath and shower spaces have minimum clearances illustrated in figure IRC Section 307.1


If you have any questions regarding the above comments, please contact Shelley Knuffke at (520) 576-8400 between 8:00 A.M. to 5:00 P.M., M-F.
08/07/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2007 GERARDO BONILLA OUT TO CUSTOMER Completed