Permit Number: T07CM02769
Parcel: 12706010A

Address:
40 N SWAN RD 02

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02769
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02769 6/28/07

1. Provide the size for the new feeder to the relocated panel.
2. Revisit your fault calculations depending on the size of the new feeder.
3. It appears that what is marked as "Electrical Service" on the Key Site Plan may be the transformer, not the building service entrance.
4. Circuit A-28 has a receptacle, not just a space.
5. It appears that the load on Circuit 16 is 540VA, not 360VA.
06/28/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2006 mechanical code has not yet been adopted; this review is based on the 2003 IMC.
2. Include the calculation for common ventilation per Section 403.3.2, IMC 2003.
06/28/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The current code is the 2003 UPC; the 2006 IPC has not yet been adopted.
06/28/2007 ROBERT SHERRY WATER REVIEW Approved
06/28/2007 ANY ENGINEERING REVIEW Approved
06/29/2007 GBONILL1 ZONING REVIEW Needs Review
06/29/2007 GBONILL1 WWM REVIEW Needs Review
06/29/2007 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
06/29/2007 GBONILL1 FIRE REVIEW Needs Review
06/29/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review