Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02769
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02769 6/28/07 1. Provide the size for the new feeder to the relocated panel. 2. Revisit your fault calculations depending on the size of the new feeder. 3. It appears that what is marked as "Electrical Service" on the Key Site Plan may be the transformer, not the building service entrance. 4. Circuit A-28 has a receptacle, not just a space. 5. It appears that the load on Circuit 16 is 540VA, not 360VA. |
| 06/28/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The 2006 mechanical code has not yet been adopted; this review is based on the 2003 IMC. 2. Include the calculation for common ventilation per Section 403.3.2, IMC 2003. |
| 06/28/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The current code is the 2003 UPC; the 2006 IPC has not yet been adopted. |
| 06/28/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/28/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 06/29/2007 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 06/29/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 06/29/2007 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/29/2007 | GBONILL1 | FIRE | REVIEW | Needs Review | |
| 06/29/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |