Permit Number: T07CM02757
Parcel: 136048320

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02757
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/28/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/28/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/06/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. COMMENTS REGARDING LIGHTING CODE COMPLIANCE MADE ON PREVOUS REVIEWS. Fixture A as specified on the Luminaire Schedule and Outdoor Lighting calculation, 150W incandescent, is in violation of the 2006 IECC, Section 505.6.1.
2. Cut sheets for two different fixtures have been submitted. One is a 26W fluorescent, the other is 150W max. Clarify.
05/13/2008 HEATHER THRALL ZONING REVIEW Approved
05/13/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved