Permit Number: T07CM02732
Parcel: 105102430

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM02732
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the text size on all plan sheets to a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson. COMMENT REMAINS: All E sheets appear to require an adjustment to the size of the lettering.

2) Please provide verification that the egress illumination with emergency power has been provided in accordance with section 1006.3 of the 2003 IBC. Sheet E0.1 appears to indicate that some of the fixtures that have been provided with emergency power will be replaced, but sheet E1 denotes significantly fewer fixtures with emergency power. Please revise accordingly. COMMENT REMAINS: It does not appear the comments from the review were addressed. Please identify on the plans the location of the changed lighting.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/15/2007 CINDY AGUILAR OUT TO CUSTOMER Completed