Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02732
Parcel: 105102430

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM02732
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2007 DAVE MANN FIRE REVIEW Approved
07/16/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/24/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the text size on all plan sheets to a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson.

2) Please provide verification that the egress illumination with emergency power has been provided in accordance with section 1006.3 of the 2003 IBC. Sheet E0.1 appears to indicate that some of the fixtures that have been provided with emergency power will be replaced, but sheet E1 denotes significantly fewer fixtures with emergency power. Please revise accordingly.

3) Please coordinate the denoted scope of work specified on sheet AA with the information provided within the plans per section 106.1.1 of the 2003 IBC. The current submittal denotes the scope of work to be a 23,427 sf interior build-out.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2007 VFLORES1 OUT TO CUSTOMER Completed