Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM02728
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/10/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/10/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the specified exhaust fan will provide the proposed air flow. 2. Correct the ventilation calculations and include the correction for common ventilation. The only way that the nail salon area (critical space) could have a 0.2 fraction of outside air would be if it was supplied with 500 CFM of supply air. Footnote b of Table 403.3 requires no recirculation of the air supplied to the nail salon area. Provide sufficient data for evaluation. |
07/10/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/16/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |