Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02728
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 06/26/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/27/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide local exhaust for the foot spa. 2. Update the ventilation calculations to the 2006 IMC. 3. Provide calculations to show that the specified exhaust fan will provide the proposed air flow. 4. Correct the ventilation calculations and include the correction for common ventilation. |
| 06/27/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please provide verification on the plans that 20% of the work has been spent upgrading the accessibility of the facility or verify that the entire facility is 100% accessible in accordance with section 3409.7 of the 2006 IBC. 2) Please provide verification that the nail station complies with section 904 of ANSI 117.1-2003. |
| 06/27/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a drinking fountain per Chapter 2900, IBC 2006. 2. Revise the water riser diagram to show a source of water. |
| 06/27/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/10/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 07/10/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |