Permit Number: T07CM02728
Parcel: 119046070

Address:
502 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02728
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2007 HEATHER THRALL ZONING REVIEW Approved
06/26/2007 LOREN MAKUS ENGINEERING REVIEW Approved
06/27/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide local exhaust for the foot spa.
2. Update the ventilation calculations to the 2006 IMC.
3. Provide calculations to show that the specified exhaust fan will provide the proposed air flow.
4. Correct the ventilation calculations and include the correction for common ventilation.
06/27/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please provide verification on the plans that 20% of the work has been spent upgrading the accessibility of the facility or verify that the entire facility is 100% accessible in accordance with section 3409.7 of the 2006 IBC.

2) Please provide verification that the nail station complies with section 904 of ANSI 117.1-2003.
06/27/2007 ROBERT SHERRY WATER REVIEW Approved
06/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a drinking fountain per Chapter 2900, IBC 2006.
2. Revise the water riser diagram to show a source of water.
06/27/2007 DAVE MANN FIRE REVIEW Approved
07/10/2007 CAGUILA1 WWM REVIEW Needs Review
07/10/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review