Permit Number - T07CM02714
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM02714 8/9/07 1. CU bond from the transformer shall be sized at #2, not #4. Reference NEC Table 250.66 Note b. |