Permit Number: T07CM02714
Parcel: 14024058H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02714
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please provide structural verification that the existing structural system can support the new heaters in accordance with section 106.1.1 of the 2003 IBC. Comment Remains.

2) Provide accessible details for the drinking fountain in order to verify compliance with section 602 of ANSI 117.1-2003. Please be aware that a wall mounted drinking fountain typically creates a horizontal projection in violation of section 1003.3.3 of the 2003 IBC. Comment Remains.
07/03/2007 DAVE MANN FIRE REVIEW Approved
07/03/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/03/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02714 7/3/07

Reference Comment #5 on previous review. Since this is to remain a Warehouse, please apply 0.8 W/SF for the IECC calculations, not 1.2. Revisit lighting design accordingly.
07/20/2007 GBONILL1 WWM REVIEW Needs Review