Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02714
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please provide structural verification that the existing structural system can support the new heaters in accordance with section 106.1.1 of the 2003 IBC. Comment Remains. 2) Provide accessible details for the drinking fountain in order to verify compliance with section 602 of ANSI 117.1-2003. Please be aware that a wall mounted drinking fountain typically creates a horizontal projection in violation of section 1003.3.3 of the 2003 IBC. Comment Remains. |
| 07/03/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/03/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/03/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02714 7/3/07 Reference Comment #5 on previous review. Since this is to remain a Warehouse, please apply 0.8 W/SF for the IECC calculations, not 1.2. Revisit lighting design accordingly. |
| 07/20/2007 | GBONILL1 | WWM | REVIEW | Needs Review |