Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02714
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please provide the dimensions for the rear grab bar in order to verify compliance with section 604.5.2 of ANSI 117.1-2003. 2) Please provide structural verification that the existing structural system can support the new heaters in accordance with section 106.1.1 of the 2003 IBC. 3) Coordinate the location of the drinking fountain within the plans per section 106.1.1 of the 2003 IBC. 4) Provide accessible details for the drinking fountain in order to verify compliance with section 602 of ANSI 117.1-2003. Please be aware that a wall mounted drinking fountain typically creates a horizontal projection in violation of section 1003.3.3 of the 2003 IBC. |
| 06/26/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02714 6/26/07 1. Provide a circuit for the Electric Water Cooler, EWC-iH. Reference Sheet P3.0. 2. Please eliminate the redundant GROUND between the CT Can and the Service Disconnect. Reference NEC 250.24 (B). 3. Total allowable lumens appear to be 268,000, not 25192. 4. There are 6 Fixtures C, not 5. Please correct Outdoor Lighting Code Compliance Code Schedule. 5. If Industrial Work is the intent, as indicated by the classification of area in the IECC Lighting Code Compliance, it appears that a change of occupancy for this building is in order. |
| 06/26/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/26/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 06/26/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Size natural gas pipe per Section 1217.1, UPC 2003 or provide calculations demonstrating conformance to Section 1217.3, UPC 2003. 2. Coordinate details 203 and 205 with the plumbing plans; show how the water heater is to be plumbed and the water temperature controlled. 3. Tucson Water does not provide ¾" meters, they have 5/8" and 1" meters. |
| 07/03/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 07/03/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/03/2007 | DROBEY1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/03/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 07/03/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 07/03/2007 | DELMA ROBEY | REJECT SHELF | Completed |