Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide material standards for all plumbing fixtures being provided by others (e.g. hand sinks and mop sink). Reference: Section 401.1, UPC 2003.
2. Provide a description for the mop sink faucet. Reference: Section 401.1, UPC 2003.
3. Specify the type of backflow prevention devices to be used for each appliance connection to the water distribution system. Reference: Section 603.0, UPC 2003.
05/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/22/2008 GERRY KOZIOL WWM REVIEW Approved