Permit Number: T07CM02711
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02711
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2007 MARTIN BROWN FIRE REVIEW Approved
06/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide balancing data for the restroom exhaust (i.e. how many cfm for the men's, how many cfm for the women's).
06/26/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Complete the water pressure calculations shown on sheet P1.0. Reference Section 103.2.3, UPC 2003.
2. Complete the waste and vent isometrics. Reference Section 103.2.3, UPC 2003.
3. Show that the floor of the restroom slopes toward the floor drain. Reference Section 412.2, UPC 2003.
4. "Waterless" urinals are not Code-compliant fixtures. Reference Sections 211.0, 406.2, 406.3, 601.1, and 1005.0, UPC 2003.
5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
6. Provide an upper terminal cleanout for the floor sink located in the lobby. Reference Section 707.4, UPC 2003.
06/26/2007 ROBERT SHERRY WATER REVIEW Approved
06/26/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please coordinate all toilet room dimensions with the accessiblity details on sheet A2.0 and in accordance with section 604 of ANSI 117.1-2003.

2) Please revise the connection details for the new monitors per section 1604.1 of the 2003 IBC.

3) Please revise doors 2 & 3 to comply with section 1008.1.8.3 of the 2003 IBC as only the main door is permitted to have keyed cylinders and the applicable signage.

4) Please provide stuctural calculations and appropriate plans, sections and details to provide sufficient information regarding the addition on the southeast side per section 106.1.1 of the 2003 IBC.

5) Please specify the vertical placement of the vertical grab bar in accordance with section 604.5.1 of ANSI 117.1-2003.

6) Please revise the self-serve drink station to eliminate the horizontal projection per section 1003.3.3 of the 2003 IBC.
07/05/2007 DROBEY1 WWM REVIEW Needs Review
07/05/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM02711 6/26/07

1. Provide an electrical circuit for the new Exhaust Fan.
07/05/2007 DROBEY1 ENGINEERING REVIEW Needs Review
07/05/2007 DROBEY1 ZONING REVIEW Needs Review
07/05/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/05/2007 DELMA ROBEY APPROVAL SHELF Completed
07/05/2007 DELMA ROBEY OUT TO CUSTOMER Completed
07/05/2007 DELMA ROBEY REJECT SHELF Completed