Permit Number: T07CM02705
Parcel: 117022480

Address:
940 N 4TH AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM02705
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM02705

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes).

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" The revised plans may show only the final version information for clarity. The originally approved plans serve as a record of previous version.
" State the need for wall and ceiling insulation for a screened porch, R301.1.
" Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1.

STRUCTURAL PLANS:

1. Provide a complete braced panel layout showing panels at the ends (within 12.5') if wall screen openings will be surfaced with glass, Table R602.10.1.
2. Provide floor girder (beam) sized for the stated 12' span with a 6'2" tributary load shown on sheet F2, R502.5. May require the deleting of the Doug Fir #2 notation.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show the thermal envelop for the porch if enclosing with glazing is intended. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "R" values of insulation and the "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.40, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2008 DELMA ROBEY OUT TO CUSTOMER Completed
03/21/2008 SHANAE POWELL REJECT SHELF Completed