Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM02703
Parcel: 137055240

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T07CM02703
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2007 MICHAEL ST. PAUL ZONING REVIEW Denied The last approved site plan / Development Plan is required.
06/25/2007 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
06/25/2007 THAUSER1 FIRE REVIEW Needs Review
06/25/2007 LOREN MAKUS ENGINEERING REVIEW Needs Review Last approved site plan require before approval can be given.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2007 THAUSER1 OUT TO CUSTOMER Completed