Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM02700
Parcel: 12801007A

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM02700
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the text size on all plan sheets to a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson. COMMENT REMAINS: All E sheets appear to require an adjustment to the size of the lettering.

2) Please provide verification that the egress illumination with emergency power has been provided in accordance with section 1006.3 of the 2003 IBC. Sheet E0.1 appears to indicate that some of the fixtures that have been provided with emergency power will be replaced, but sheet E1 fails to indicate the existance of emergency power for the replacement fixtures. Please revise accordingly. COMMENT REMAINS: It does not appear the comments from the review were addressed. Please identify on the plans the location of the changed lighting.
11/15/2007 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review