Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM02700
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please revise the text size on all plan sheets to a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson. COMMENT REMAINS: All E sheets appear to require an adjustment to the size of the lettering. 2) Please provide verification that the egress illumination with emergency power has been provided in accordance with section 1006.3 of the 2003 IBC. Sheet E0.1 appears to indicate that some of the fixtures that have been provided with emergency power will be replaced, but sheet E1 fails to indicate the existance of emergency power for the replacement fixtures. Please revise accordingly. COMMENT REMAINS: It does not appear the comments from the review were addressed. Please identify on the plans the location of the changed lighting. |
| 11/15/2007 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |