Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02700
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/27/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
07/09/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
07/13/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ELECTRICAL COMMENTS ON T07CM02700,5550 E BROADWAY ,TUCSON AZ. 1. SHEET E-2, THE CIRCUITRY SHOWN ON THIS PAGE IS GOING TO THE WRONG PANELS,REVIEW THESE CIRCUITS AND LABEL THEM AS GOING TO THE CORRECT PANELS AND RESUBMIT |
07/24/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please revise the text size on all plan sheets to a minimum of 1/8" in accordance with the submittal requirements for the City of Tucson. 2) Please provide verification that the egress illumination with emergency power has been provided in accordance with section 1006.3 of the 2003 IBC. Sheet E0.1 appears to indicate that some of the fixtures that have been provided with emergency power will be replaced, but sheet E1 fails to indicate the existance of emergency power for the replacement fixtures. Please revise accordingly. 3) Please coordinate the denoted scope of work specified on sheet AA with the information provided within the plans per section 106.1.1 of the 2003 IBC. The current submittal denotes the scope of work to be a 23,500 sf interior build-out. |
07/31/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | 1 |