Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02684
Parcel: 12215312A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02684
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/26/2007 MARTIN BROWN FIRE REVIEW Approved
07/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the potable water is connected to the baptismal pool. Reference Sections 103.2.3 and 603.0, UPC 2003.
2. Provide a connection to the drainage system (not the condensate drains) of the building for all plumbing fixtures (e.g. drinking fountain). Reference Section 304.0, UPC 2003.
3. Clarify the meaning of the phrase, "…scored inside of pipe clean". Reference Section 103.2.3, UPC 2003.
07/10/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the location of the funnel drains and, if they are located in the return air plenums, how will they be prevented from becoming a contaminant source due to the direct connection to the dry well. Reference Sections 106.2.1 and 401.7, IMC 2003.
2. Clarify that the construction of the return air plenums will comply with the requirements of Section 602.2, IMC 2003.
3. Show how outside air is to be provided for ventilation of the conditioned spaces. Reference Section 401.2, IMC 2003.
07/10/2007 ROBERT SHERRY WATER REVIEW Denied Provide information to show that the water service to this building is equipped with an approved backflow prevention assembly. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
07/12/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/12/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied Provide future site visibility triangles and label accordingly. It appears the wall is within the future SVT.

A site plan review may be required in addition to the building review.
07/19/2007 TERRY STEVENS ZONING REVIEW Approved
07/23/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" FONT ALL CAPITAL LETTERS REQUIRED ON STRUCTURAL PAGES.

2. PROVIDE CUT SHEET FOR FERRULE RING TO VERIFY 2500 LB PULL FORCE.

3. PRESUMPTIVE PASSIVE PRESSURE FOR RETAINING WALLS IS 250 PCF WITHOUT A SOILS REPORT. (CITY AMENDMENT 1804.2.1)

4. CORRECT CUT SECTION CALL OUTS DETAIL 3/S1 TO ACCURATELY REFLECT COLUMN LINE AND BUILDING ATTACHMENT. (CURRENTLY COL LINE CUT IS SHOWN AT BUILDING ATTACH).

5. PROVIDE INFORMATION IN DETAILS PP A11 ON HOW ALL THIS FRAMING IS FASTENED TOGETHER.

6. PROVIDE CALCULATIONS FOR MECHANICAL ROOM FLOOR INCLUDING DEAD AND LIVE LOADS.

7. PROVIDE LEDGER ATTACHMENT INFORMATION FOR DETAIL 5/A10.

8. MODIFYING PULPIT, BAPTISMAL AND PLATFORM REQUIRES THAT YOU PROVIDE ACCESSIBILITY PER CHAPTER 11 OF THE IBC.

9. REPLACING GUARD AT CHOIR LOFT REQUIRES COMPLIANCE WITH 42" MIN. HEIGHT.

10. PROVIDE DETAILS FOR KEYNOTE 1, CHOIR LOFT FLOOOR PLAN PP A5.

11. PROVIDE DETAILS FOR KEYNOTE 7, CHOIR LOFT DEMOLITION PLAN PP A5.

12. CLARIFY REFERENCE TO IBC 1003.2.12 ON PP A8. GUARD CONSTRUCTION EXCEPTION 5 OF 1012.1 DOES NOT SEEM TO APPLY TO THIS CONDITION.

13. INDICATE ON PLANS # OF PLUMBING FACILITIES AND RELATIVE LOCATION IN RELATION TO SANCTUARY. PLEASE DO NOT REFERENCE A PAST ACTIVITY #.

14. INDICATE ON PLAN THAT FACILITY WILL BE 100% ACCESSIBLE OR INDICATE HOW SECTION 3409.6 EXCEPTION 1 IS BEING MET.
07/25/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2007 THAUSER1 OUT TO CUSTOMER Completed
09/07/2007 THAUSER1 REJECT SHELF Completed